Vue de la page 0
Manual #5403550 - Rev Q
11/12
St. Louis, MO
(866) 956-0988
www.pottersignal.com
PFC-4410RC
Releasing Panel for
Water and Agent
Extinguishing
Systems
Installation, Operation, and
Instruction Manual
(All specications subject to revision.)
Vue de la page 0
1 2 3 4 5 6 ... 98 99

Résumé du contenu

Page 1 - Instruction Manual

Manual #5403550 - Rev Q11/12St. Louis, MO(866) 956-0988 www.pottersignal.comPFC-4410RCReleasing Panel for Water and Agent Extinguishing SystemsInstall

Page 2 - WARRANTY INFORMATION

10PFC-4410RC • 5403550 • REV Q • 11/12Control Buttons• Signal Silence - Momentary, silences signaling circuits, (except those activated by zones pro

Page 3 - Co n t e n t s

11PFC-4410RC • 5403550 • REV Q • 11/12circuit would be used that would be programmed to operate whenever the release circuit is activated. Equivalen

Page 4

12PFC-4410RC • 5403550 • REV Q • 11/12Backup Power Requirements• PFC-4410RC - Standby 121 mA, alarm 274 mA at 24VDC, supervisedService UseNFPA 12 – C

Page 5 - Installation Precautions

13PFC-4410RC • 5403550 • REV Q • 11/12The annunciator also has a lamp test switch.ARM-44 (Relay Module) - Relay installs in a cabinet and provides 8

Page 6 - Fire Alarm System Limitations

14PFC-4410RC • 5403550 • REV Q • 11/12scrolling through all of the events by use of the scroll up and scroll down buttons. The LED will go steady af

Page 7

15PFC-4410RC • 5403550 • REV Q • 11/12 4. Activation of yellow POWER TROUBLE indicator on LED annunciator module. 5. Activation of yellow SYSTEM TR

Page 8 - 3006230

16PFC-4410RC • 5403550 • REV Q • 11/12Lamp TestWhen the panel is in a Normal Condition, pushing the two top buttons will illuminate all of the LED&ap

Page 9 - PFC-4410RC Visual Indicators

17PFC-4410RC • 5403550 • REV Q • 11/125. Move the PROGRAM switch down. The LCD should respond: “LOOK AT HISTORY?”. Press the bottom button until the

Page 10 - Notication/Release Circuits

18PFC-4410RC • 5403550 • REV Q • 11/12There is no capability to back up screens in the program mode. If a mistake was made during programming, move

Page 11 - Input Power

19PFC-4410RC • 5403550 • REV Q • 11/12PasswordThis display prevents unauthorized programming of the panel by requiring the user to enter the proper p

Page 12

2PFC-4410RC • 5403550 • REV Q • 11/12Potter Electric Signal Company, LLC St. Louis, MO • (866) 956-0988WARRANTY INFORMATIONThe essential purpose of

Page 13 - Supervisory

20PFC-4410RC • 5403550 • REV Q • 11/12One Man WalktestThis display allows the user to select system mode NORMAL or ONE MAN WALKTEST by pressing the

Page 14 - Loss or Reduction of AC Power

21PFC-4410RC • 5403550 • REV Q • 11/12PFC-4410RC Standard Program InformationThe PFC-4410RC has 24 standard programs which are detailed in the follow

Page 15

22PFC-4410RC • 5403550 • REV Q • 11/12See page 89 or label inside panel door for smoke detector compatibility data.See page 85 for battery informati

Page 16 - Test Procedure (Canada)

23PFC-4410RC • 5403550 • REV Q • 11/12Program #1 Mode1. Apply power to panel.2. Move the program switch down.3. Press the FUNCTION (bottom) button un

Page 17 - Panel Visual Display

24PFC-4410RC • 5403550 • REV Q • 11/12+OUTPUT1BATT2OUTPUTASSYDIODEEOLOUTPUT3 4OUTPUTREDBLACKNOCOMNCNCNONONOCOMCOMCOM--+++ - + - + -LIMITED ANDNON-POW

Page 18 - Date and Time

25PFC-4410RC • 5403550 • REV Q • 11/12Program #2 Mode1. Apply power to panel.2. Move the program switch down.3. Press the FUNCTION (bottom) button un

Page 19 - Output Enable/Disable

26PFC-4410RC • 5403550 • REV Q • 11/12See page 89 or label inside panel door for smoke detector compatibility data.See page 85 for battery informati

Page 20 - One Man Walktest

27PFC-4410RC • 5403550 • REV Q • 11/12Program #3 Mode1. Apply power to panel.2. Move the program switch down.3. Press the FUNCTION (bottom) button un

Page 21

28PFC-4410RC • 5403550 • REV Q • 11/12OBSERVE POLARITY WHEN CONNECTING SMOKE DETECTORS5.1KEOLR5.1KEOLR5.1KEOLR5.1KEOLR5.1KEOLRPS10ALOW AIRPS10AVALVET

Page 22 - Wiring Diagram Program #1

29PFC-4410RC • 5403550 • REV Q • 11/12Program #4 Mode1. Apply power to panel.2. Move the program switch down.3. Press the FUNCTION (bottom) button un

Page 23 - Program #1 Mode

3PFC-4410RC • 5403550 • REV Q • 11/12Co n t e n t sInstallation Precautions ...

Page 24 - Wiring Diagram Program #2

30PFC-4410RC • 5403550 • REV Q • 11/12OBSERVE POLARITY WHEN CONNECTING SMOKE DETECTORS5.1KEOLR5.1KEOLR5.1KEOLR5.1KEOLR5.1KEOLRPS10ALOW AIRPS10AVALVET

Page 25 - Program #2 Mode

31PFC-4410RC • 5403550 • REV Q • 11/12Program #5 Mode1. Apply power to panel.2. Move the program switch down.3. Press the FUNCTION (bottom) button un

Page 26 - Wiring Diagram Program #3

32PFC-4410RC • 5403550 • REV Q • 11/12OBSERVE POLARITY WHEN CONNECTING SMOKE DETECTORS5.1KEOLR5.1KEOLR5.1KEOLR5.1KEOLR5.1KEOLRPS10APS10 OR PS40AUX.PO

Page 27 - Program #3 Mode

33PFC-4410RC • 5403550 • REV Q • 11/12Program #6 Mode1. Apply power to panel.2. Move the program switch down.3. Press the FUNCTION (bottom) button un

Page 28 - Wiring Diagram Program #4

34PFC-4410RC • 5403550 • REV Q • 11/12OBSERVE POLARITY WHEN CONNECTING SMOKE DETECTORS5.1KEOLR5.1KEOLR5.1KEOLR5.1KEOLRPS10A5.1KEOLRPS10 OR PS40EOLRVA

Page 29 - Program #4 Mode

35PFC-4410RC • 5403550 • REV Q • 11/12Program #7 Mode1. Apply power to panel.2. Move the program switch down.3. Press the FUNCTION (bottom) button un

Page 30 - Wiring Diagram Program #5

36PFC-4410RC • 5403550 • REV Q • 11/12S+--+++ - + - + --+-+-+ + -- -+ -+ -+ -+ -++ - + - + -5.1KEOLR5.1KEOLR5.1KEOLR5.1KEOLR5.1KEOLRPS10AVA LV ETAMPE

Page 31 - Program #5 Mode

37PFC-4410RC • 5403550 • REV Q • 11/12Program #8 Mode1. Apply power to panel.2. Move the program switch down.3. Press the FUNCTION (bottom) button un

Page 32 - Wiring Diagram Program #6

38PFC-4410RC • 5403550 • REV Q • 11/12OBSERVE POLARITY WHEN CONNECTING SMOKE DETECTORS5.1KEOLR5.1KEOLR5.1KEOLR5.1KEOLRPS10A5.1KEOLRPS10AEOLRPS10AAND/

Page 33 - Program #6 Mode

39PFC-4410RC • 5403550 • REV Q • 11/12Program #9 Mode1. Apply power to panel.2. Move the program down.3. Press the FUNCTION (bottom) button until the

Page 34 - Wiring Diagram Program #7

4PFC-4410RC • 5403550 • REV Q • 11/12PFC-4410RC Connection Drawing ...

Page 35 - Program #7 Mode

40PFC-4410RC • 5403550 • REV Q • 11/12OBSERVE POLARITY WHEN CONNECTING SMOKE DETECTORSEOLR5.1KEOLR5.1KEOLR5.1KEOLR5.1KEOLR5.1KEOLROSYSUPCVSPS10AAUX.P

Page 36 - Wiring Diagram Program #8

41PFC-4410RC • 5403550 • REV Q • 11/12Program #10 Mode1. Apply power to panel.2. Move the program down.3. Press the FUNCTION (bottom) button until th

Page 37 - Program #8 Mode

42PFC-4410RC • 5403550 • REV Q • 11/12See page 89 or label inside panel door for smoke detector compatibility data.See page 85 for battery informatio

Page 38 - Wiring Diagram Program #9

43PFC-4410RC • 5403550 • REV Q • 11/12Program #11 Mode1. Apply power to panel.2. Move the program switch down.3. Press the FUNCTION (bottom) button u

Page 39 - Program #9 Mode

44PFC-4410RC • 5403550 • REV Q • 11/12S+--+++ - + - + --+-+-+ + -- -+ -+ -+ -+ -++ - + - + -5.1KEOLR5.1KEOLR5.1KEOLR5.1KEOLR5.1KEOLRPS10AVA LV ETAMPE

Page 40 - Wiring Diagram Program #10

45PFC-4410RC • 5403550 • REV Q • 11/12Program #12 Mode1. Apply power to panel.2. Move the program switch down.3. Press the FUNCTION (bottom) button u

Page 41 - Program #10 Mode

46PFC-4410RC • 5403550 • REV Q • 11/12OBSERVE POLARITY WHEN CONNECTING SMOKE DETECTORS5.1KEOLR5.1KEOLR5.1KEOLR5.1KEOLR5.1KEOLROSYSUPCVSPS10AEOLROPTIO

Page 42 - Wiring Diagram Program #11

47PFC-4410RC • 5403550 • REV Q • 11/12Program #13 Mode1. Apply power to panel.2. Move the program switch down.3. Press the FUNCTION (bottom) button u

Page 43 - XX = Cross-Zoned

48PFC-4410RC • 5403550 • REV Q • 11/12QRS-ALARM ZONEQRSSUPERVISORYZONE5.1KEOLR5.1KEOLR5.1KEOLR5.1KEOLR5.1KEOLR5.1KAUX.POWER24VR DCSUP 1/ABORTSUPV 2ZO

Page 44 - Wiring Diagram Program #12

49PFC-4410RC • 5403550 • REV Q • 11/12Program #14 Mode1. Apply power to panel.2. Move the program switch down.3. Press the FUNCTION (bottom) button u

Page 45 - Program #12 Mode

5PFC-4410RC • 5403550 • REV Q • 11/12The abort circuit will not abort the release or stop the predischarge timer activated by zones programmed as MAN

Page 46 - Wiring Diagram Program #13

50PFC-4410RC • 5403550 • REV Q • 11/12PANEL INPUTS (INITIATING ZONES) CONNECT TO NORMALLY OPEN DEVICES OR COMPATIBLE 2 WIRE SMOKE DETECTORS.MAXIMUM L

Page 47 - Program #13 Mode

51PFC-4410RC • 5403550 • REV Q • 11/12Program #15 Mode1. Apply power to panel.2. Move the program switch down.3. Press the FUNCTION (bottom) button u

Page 48 - 2 Supervisory Zones

52PFC-4410RC • 5403550 • REV Q • 11/12The following programs are for chemical or gas extinguishing systems. Selecting the CHEMICAL mode allows the u

Page 49 - Program #14 Mode

53PFC-4410RC • 5403550 • REV Q • 11/12th i s p a g e i n t e n t i o n a l l y l e f t b l a n k .

Page 50 - Supervisory Zones

54PFC-4410RC • 5403550 • REV Q • 11/12PANEL INPUTS (INITIATING ZONES) CONNECT TO NORMALLY OPEN DEVICES OR COMPATIBLE 2 WIRE SMOKE DETECTORS.MAXIMUM L

Page 51 - Program #15 Mode

55PFC-4410RC • 5403550 • REV Q • 11/12Program #20 Mode1. Apply power to panel.2. Move the program switch down.3. Press the FUNCTION (bottom) button u

Page 52

56PFC-4410RC • 5403550 • REV Q • 11/12PANEL INPUTS (INITIATING ZONES) CONNECT TO NORMALLY OPEN DEVICES OR COMPATIBLE 2 WIRE SMOKE DETECTORS.MAXIMUM L

Page 53

57PFC-4410RC • 5403550 • REV Q • 11/12Program #21 Mode1. Apply power to panel.2. Move the program switch down.3. Press the FUNCTION (bottom) button u

Page 54 - Wiring Diagram Program #20

58PFC-4410RC • 5403550 • REV Q • 11/12OBSERVE POLARITY WHEN CONNECTING SMOKE DETECTORS5.1KVALVETAMPEROSYSUPCVS5.1KEOLR5.1KEOLR5.1KEOLR5.1KEOLR5.1KEOL

Page 55 - Program #20 Mode

59PFC-4410RC • 5403550 • REV Q • 11/12Program #22 Mode1. Apply power to panel.2. Move the program switch down.3. Press the FUNCTION (bottom) button u

Page 56 - Wiring Diagram Program #21

6PFC-4410RC • 5403550 • REV Q • 11/12Design GuidelinesPeople trained in the design of special hazard systems shall determine the selection and placem

Page 57 - Program #21 Mode

60PFC-4410RC • 5403550 • REV Q • 11/12See page 89 or label inside panel door for smoke detector compatibility data.See page 85 for battery informati

Page 58 - Conrmation Zone

61PFC-4410RC • 5403550 • REV Q • 11/12Program #23 Mode1. Apply power to panel.2. Move the program switch down.3. Press the FUNCTION (bottom) button u

Page 59 - Program #22 Mode

62PFC-4410RC • 5403550 • REV Q • 11/12OBSERVE POLARITY WHEN CONNECTING SMOKE DETECTORS5.1KVALVETAMPEROSYSUPCVS5.1KEOLR5.1KEOLR5.1KEOLR5.1KEOLR5.1KEOL

Page 60 - Wiring Diagram Program #23

63PFC-4410RC • 5403550 • REV Q • 11/12Program #24 Mode1. Apply power to panel.2. Move the program switch down.3. Press the FUNCTION (bottom) button u

Page 61 - Program #23 Mode

64PFC-4410RC • 5403550 • REV Q • 11/12PANEL INPUTS (INITIATING ZONES) CONNECT TO NORMALLY OPEN DEVICES OR COMPATIBLE 2 WIRE SMOKE DETECTORS.MAXIMUM L

Page 62 - Wiring Diagram Program #24

65PFC-4410RC • 5403550 • REV Q • 11/12Program #25 Mode1. Apply power to panel.2. Move the program switch down.3. Press the FUNCTION (bottom) button u

Page 63 - Program #24 Mode

66PFC-4410RC • 5403550 • REV Q • 11/12OBSERVE POLARITY WHEN CONNECTING SMOKE DETECTORS5.1KVALVETAMPEROSYSUPCVS5.1KEOLR5.1KEOLR5.1KEOLR5.1KEOLR5.1KEOL

Page 64 - Wiring Diagram Program #25

67PFC-4410RC • 5403550 • REV Q • 11/12Program #26 Mode1. Apply power to panel.2. Move the program switch down.3. Press the FUNCTION (bottom) button u

Page 65 - Program #25 Mode

68PFC-4410RC • 5403550 • REV Q • 11/12See page 89 or label inside panel door for smoke detector compatibility data.See page 85 for battery informati

Page 66 - 2 eAEROSOL Circuits

69PFC-4410RC • 5403550 • REV Q • 11/12Program #27 Mode1. Apply power to panel.2. Move the program switch down.3. Press the FUNCTION (bottom) button u

Page 67 - Program #26 Mode

7PFC-4410RC • 5403550 • REV Q • 11/12· Supervisory Zones· Supervisory· Tamper· Low Air Supervisory· High Air· Low Air AlarmNOTE: Only zones pro

Page 68 - Wiring Diagram Program #27

70PFC-4410RC • 5403550 • REV Q • 11/12OBSERVE POLARITY WHEN CONNECTING SMOKE DETECTORS5.1KVALVETAMPEROSYSUPCVS5.1KEOLR5.1KEOLR5.1KEOLR5.1KEOLR5.1KEOL

Page 69 - Program #27 Mode

71PFC-4410RC • 5403550 • REV Q • 11/12Program #28 Mode1. Apply power to panel.2. Move the program switch down.3. Press the FUNCTION (bottom) button u

Page 70 - Wiring Diagram Program #28

72PFC-4410RC • 5403550 • REV Q • 11/12CUSTOM PROGRAMZONESSUP 1/ABORT SUP 2 #1 #2 #3 #4OUTPUTS *Supervisory or AbortSupervisory#1#2#3 #4* If SUP

Page 71 - Program #28 Mode

73PFC-4410RC • 5403550 • REV Q • 11/12PFC-4410RC Custom Program Information for Water Based Extinguishing SystemsIf the user has selected program # 0

Page 72 - Wiring Diagram Custom Program

74PFC-4410RC • 5403550 • REV Q • 11/12After describing all initiating zones or skipping to the next function, the following will appear in the displa

Page 73 - Initiating Zone Description

75PFC-4410RC • 5403550 • REV Q • 11/12Where “<a>” is the number of the releasing circuit output.Normal/Cross-ZoningEach releasing circuit can b

Page 74 - Output Description

76PFC-4410RC • 5403550 • REV Q • 11/12After all available outputs for the zone displayed are mapped, the display will automatically change to the nex

Page 75 - Releasing Output Time

77PFC-4410RC • 5403550 • REV Q • 11/12PFC-4410RC Custom Program Information For Chemical Based Extinguishing SystemsIf the user has selected program

Page 76 - Custom Message

78PFC-4410RC • 5403550 • REV Q • 11/12Zone 5 is a supervisory or abort zone and can only be described as SUPERVISORY, TAMPER, LOW AIR or HIGH AIR, o

Page 77

79PFC-4410RC • 5403550 • REV Q • 11/12 Where “<a>” is the num

Page 78

8PFC-4410RC • 5403550 • REV Q • 11/12· Signal Silence button· Buzzer Silence button· Manual event scroll buttons· Automatic resound of silenced t

Page 79 - First Or Second Alarm

80PFC-4410RC • 5403550 • REV Q • 11/12FUNCTION Press the bottom button to skip to the next function.If a zone has not been programmed as MAN

Page 80 - Abort Modes

81PFC-4410RC • 5403550 • REV Q • 11/12The next function will be displayed as follows:

Page 81 - output

82PFC-4410RC • 5403550 • REV Q • 11/12 SET Press the top button to scroll through the character set in one direction.SELEC

Page 82 - Programming Summary

83PFC-4410RC • 5403550 • REV Q • 11/12Custom Program (#0 only) • Describe Initiating Zones 1 - 4 Alarm Zones Supervisory Zones Dete

Page 83 - Installation Instructions

84PFC-4410RC • 5403550 • REV Q • 11/12Mounting Instructions1) The unit should be mounted in a convenient location, approximately 5 ft. from the oor

Page 84 - Mounting Instructions

85PFC-4410RC • 5403550 • REV Q • 11/12Inactive CircuitsAll inactive initiating device circuits and indicating appliance circuits must have the end-of

Page 85 - Battery Size Calculations

86PFC-4410RC • 5403550 • REV Q • 11/12Secondary Power Supply Requirements: Table 2 Service Use Standby Time Alarm Time NFPA 72 •

Page 86 - Current Requirements: Table 1

87PFC-4410RC • 5403550 • REV Q • 11/12Typical 2 Wire Detector Connection DrawingBase wiring for Potter models IS-24 Ionization Detectors and PS-24 Ph

Page 87 - Typical 4-Wire Wiring

88PFC-4410RC • 5403550 • REV Q • 11/12ACTIVE ALARM CONDITIONSPECIAL APPLICATIONSUPVWTRFLWPFC-4410RC Connection DrawingFor addistional information see

Page 88 - PFC-4410RC Connection Drawing

89PFC-4410RC • 5403550 • REV Q • 11/122-Wire Smoke Detector Compatibility DataSmoke Detector Compatibility Identier "A"System Sensor (Brk)

Page 89

9PFC-4410RC • 5403550 • REV Q • 11/12SpecicationsPFC-4410RC Type - 18 gauge sheet steel with hinged, removable, locked door Size - 18 1/2" x 14

Page 90 - LAMP TEST

90PFC-4410RC • 5403550 • REV Q • 11/121 Power inputs2 Battery leads3 Using the cable clamps provided, route all other wiring away from power input

Page 91 - NEC Section 760-54

91PFC-4410RC • 5403550 • REV Q • 11/12NEC Section 760-54Installation of Conductors and Equipment. (a) Separation from Electric Light, Power, Class

Page 92 - PANELPANEL

92PFC-4410RC • 5403550 • REV Q • 11/12Connection Procedure for Battery Charging Current and Voltage1) To measure the battery charging voltage: Pl

Page 93 - SSSSSSSSSSSS

93PFC-4410RC • 5403550 • REV Q • 11/12MAIN BACKUPJ4 J5 TELEPHONE CONNECTIONS U21EPROM SOCKETOUTPUT 1OUTPUT 2J11J121234NC COM

Page 94

94PFC-4410RC • 5403550 • REV Q • 11/12Smoke Detector Detector Type Standby Current (mA) Alarm Current (mA)Potter PS-24* Photoelectric .045 150Potter

Page 95

95PFC-4410RC • 5403550 • REV Q • 11/12System Sensor 2W-MOD Loop test/maint. mod. 30 50System Sensor 4W-B (12/24V) Photoelectric .05 23System Sensor 4

Page 96 - PAGE 1 OF 1PRINTED IN USA

96PFC-4410RC • 5403550 • REV Q • 11/12Annex B: Product Datasheets of Optional Equipment18” WIRE LEADS FURNISHED FOR RELAY COIL* NUMBERS REFER TO SOCK

Page 97 - MFG. #5400977 - REV N

97PFC-4410RC • 5403550 • REV Q • 11/12BLACKCONNECT ARM-2 TO OUTPUT CIRCUITREDPFC-4410RC OUTPUT TERMINALSDWG# 977-2Stock number: 3004725UL Listed:

Page 98 - PRINTED IN USA PAGE 1 OF 1

98PFC-4410RC • 5403550 • REV Q • 11/12CA2Z CLASS A INITIATING DEVICE MODULEMFG. #5401025 - REV F8/06PRINTED IN USA PAGE 1 OF 1SUPERVISORYSUPSUPZONE 1

Page 99 - PAGE 1 OF 1

99PFC-4410RC • 5403550 • REV Q • 11/12CAMCLASS A INDICATING APPLIANCE CIRCUIT MODULEThe Model CAM Class A Module is designed to be used with the PFC-