Program #10 Mode
1. Apply power to panel.
2. Move the program down.
3. Press the FUNCTION (bottom) button until the display reads “PASSWORD = 000”.
4. To enter a password, press the SELECT button until the proper number is displayed above the ^ symbol, then press the SET
button to move to the next digit. After entering the third number the display will change.
(All panels are shipped with a 000 password.)
5. Press the FUNCTION (bottom) button until the display reads “PROGRAM #0”.
6. Press the SELECT button until the display reads “PROGRAM #10”.
7. Press the SET button.
8. The panel is completely programmed except for the custom banner and zone messages. Move the program switch back up.
Description: Single Hazard, 2 detection and low air alarm zones cross-zoned*.
Inputs: 2 supervisory zones, 2 detection zone, 1 waterow zone, 1 low air alarm zone.
Outputs: 1 general alarm, 1 supervisory, 1 waterow, 1 solenoid release circuit
Operation: Activation of both detection zones and the low air alarm zone at the same time will operate the solenoid release
circuit and the general alarm bell.
Activation of either detection zone only will operate the general alarm output
Activation of the waterow zone will operate the waterow bell output
Activation of the low air alarm zone will operate the supervisory bell output. It will not operate the alarm relay
When either zone 1 or 2 is in alarm, output 1 will operate
When zone 3 is in alarm, output 2 will operate
When zone 4 is activated, output 3 will operate. This will create a supervisory condition not an alarm condition.
The alarm relay will not operate, the supervisory relay will.
When zones 1, 2 & 4 are activated at the same time, the solenoid release circuit will operate.
*Cross Zoning acceptable for NFPA 13, 15, and 16 type extinguishing systems.
PROGRAM #10
ZONES
SUP 1 SUP 2 #1 #2 #3 #4
OUTPUTS Supervisory Detection Detection Waterow Low Air
Alarm
#1 ALARM INDICATING X X
#2 ALARM INDICATING X
#3 SUPERVISORY X X X
#4 RELEASE XX XX XX
XX = Cross-Zoned