Potter PFC-4410RC Manuel d'utilisateur Page 5

  • Télécharger
  • Ajouter à mon manuel
  • Imprimer
  • Page
    / 99
  • Table des matières
  • MARQUE LIVRES
  • Noté. / 5. Basé sur avis des utilisateurs
Vue de la page 4
5
PFC-4410RC • 5403550 • REV Q • 11/12
The abort circuit will not abort the release or stop the predischarge timer activated by zones programmed as MANUAL
RELEASE. If it is desired to have the abort circuit stop the release activated from a Manual Release zone, program that zone as a
DETECTION zone instead.
High voltage electrocution hazard. Do not handle live AC wiring or work on the device while AC power is active.
This manual is designed to help with the specication, installation, and programming of the PFC-4410RC Release Panel. It is
imperative that this manual be completely read and understood before the installation or programming of the panel. Save this
manual for future reference.
Zones programmed as MANUAL RELEASE will override any cross zoning features. If it is desired to not have a manual station
override the cross zoning, program the zone as DETECTION and map accordingly.
Per ULC requirements; if this equipment is running on battery power only, it will shut off and cease to operate when the battery
voltage reaches approximatly 19-20 volts.
Fill in the name, address and telephone number of the servicing agency on the instruction sheet provided and
frame and place adjacent to control panel at eye level.
The following documentation shall be delivered to the owner or their representative upon nal acceptance of the system:
An owners manual and installation instructions covering all system equipment.
Wiring diagrams
A detailed description of the programming and operating sequence of the system
The detection and suppression system employing this release panel must be designed by people trained and competent in
the design and layout of re alarm and/or suppression systems for special hazard locations. The system shall be designed
and installed in accordance with all local and national codes and ordinances as well as the approval of the Authority Having
Jurisdiction. Only trained, qualied and competent individuals should install, program and/or service the PFC-4410RC.
Competent people would be aware of these warnings, limitations, and requirements.
Locate the panel and all system components in the following nominal environment:
* Temperature 32-120°F, Humidity 93% non-condensing.
* Verify that the wire sizes are adequate for all initiating, notication, and release circuits.
* Make certain the panel is properly grounded.
* Remove all electronic assemblies prior to any drilling, ling, reaming, or punching of the enclosure. When possible make all
cable entries from the sides, bottom, or rear of the cabinet. Verify that they will not interfere with the batteries or other components.
* The panel and system must be tested and maintained in accordance with all local and national codes and ordinances.
This is the safety alert system. It is used to alert you to potential personal injury hazards. Obey all
safety messages that follow this symbol to avoid possible injury or death.
Operating Instructions Form
Installation Precautions
Vue de la page 4
1 2 3 4 5 6 7 8 9 10 ... 98 99

Commentaires sur ces manuels

Pas de commentaire