PFC-4410RC Custom Program Information For Chemical Based Extinguishing Systems
If the user has selected program # 0 for a custom conguration of the panel the following will appear in the display window.
This display allows the user to select functions for either water or chemical based extinguishing systems. This window is for water
based, to toggle from water based to chemical based or visa versa, press the SELECT (middle) button
SET Press the top button to set the description displayed into the panels program
SELECT Press the middle button to scroll between water or chemical based modes
FUNCTION Press the bottom button to skip to the next function
After setting the CHEMICAL BASED mode or pressing FUNCTION, the following will appear in the display:
Initiating Zone Description
This allows the user to describe the initiating zones. Nine different descriptions are available. They are:
1) DETECTION - These include smoke detectors, pull stations, heat detectors and other devices put on a conventional zone.
2) WATERFLOW - Alarms from waterow zones are non-silenceable
3) LINEAR HEAT DETECTION - These use a special wire with a fuseable insulation
4) MANUAL RELEASE - Used to override cross zoning and cause instant release
5) LOW AIR ALARM – This is for a low air switch used in a double interlock system. Usually cross zoned with a smoke or heat
detector. Activation of this zone creates a supervisory condition on the panel but can still operate the release circuit.
6) SUPERVISORY - For monitoring any supervisory function as assigned
7) TAMPER - For control valve monitoring
8) LOW AIR - Used to detect low air pressure
9) HIGH AIR - Used to detect high air pressure
The rst four descriptions (DETECTION, WATERFLOW, LINEAR HEAT DETECTION and MANUAL
RELEASE) are Alarm Zones. When activated, they will put the panel into alarm and operate the appropriate output as well as
operating the alarm relay.
The 5
th
description (LOW AIR ALARM) creates a supervisory condition on the panel but can be used to activate the release
circuit, this activates the Supervisory relay not the Alarm relay.
The last four descriptions (SUPERVISORY, TAMPER, LOW AIR and HIGH AIR) are Supervisory Zones. When activated, they
will put the panel in a supervisory condition and activate any output described as “SUPERVISORY BELL”. They cannot activate
the release circuit
SET Press the top button to set the description displayed.
SELECT Press the middle button to scroll through the nine descriptions.
FUNCTION Press the bottom button to skip to the next function.
After describing all initiating zones or skipping to the next function, the following will appear in the display window:
P R O G R A M T Y P E :
W A T E R B A S E D
I N I T Z O N E # 1
D E T E C T I O N
S U P E R V S R Y 1 Z O N E
A B O R T