PFC-4410RC • 5403550 • REV Q • 11/12
2-Wire Smoke Detector Compatibility Data
Smoke Detector Compatibility Identier "A"
System Sensor (Brk) (Max. No. Of Detectors Per Zone Is 20)
Det. Model Identier Base Model Identier
1400* A N/A N/A
2400* A N/A N/A
2400TH* A N/A N/A
2W-B A N/A N/A
2WT-B A N/A N/A
2WTR-B A N/A N/A
Detection Systems (Max. No. Of Detectors Per Zone Is 25)
Det. Model Identier Base Model Identier
DS250 A MB2W/MB2WL A
DS250TH A MB2W/MB2WL A
DS250HD A MB2W/MB2WL A
Esl (Max. No. Of Detectors Per Zone Is 25)
Det. Model Identier Base Model Identier
611U S10 601U S00
611UD S10 601U S00
611UT S10 601U S00
612U S10 601U S00
612UD S10 601U S00
613U5 S10 601U S00
611UD S10 609U10 S00
612UD S10 609U10 S00
425C S10 N/A N/A
425CT S10 N/A N/A
Hochiki (Max. No. Of Detectors Per Zone Is 25)
Det. Model Identier Base Model Identier
SLR-24* HD-3 HSC-221R HB-71
HSB-221 HB-54
HSB-221N HB-54
NS6-221
NS4-221
NS6-220 HB-3
SLR-24H* HD-3 HSC-221R HB-71
HSB-221 HB-54
HSB-221N HB-54
NS6-221
NS4-221
SIJ-24* HD-3 HSC-221R HB-71
HSB-221 HB-54
HSB-221N HB-54
NS6-221
NS4-221
Fenwal (Max. No. Of Detectors Per Zone Is 25)
Det. Model Identier Base Model Identier
CPD-7051* I51FE1 2-WIRE FE51A
PSD-7155* P55FE1 2WRLT FE52A
PSD-7156* P56FE1 2WRB FE55A
All of the above Fenwal detectors and bases can be used in any combination
Retrot Base Adaptor 70-501000-003, Identier MAFE1 (for series 70-201000 Bases, Models -001, -002, -003 and -005)
Duct Housing with Detector Base DH-51, Identier DH22FE5 (for CPD-7051 and PSD-7155 detectors only)
Potter (Max. No. Of Detectors Per Zone Is 25)
Det. Model Identier Base Model Identier
PS-24* HD-3(HOCHIKI) SB-46 HB-71(HOCHIKI)
HB-54(HOCHIKI)
SB-93 HB-3 (HOCHIKI
PS-24H HD-3(HOCHIKI) SB-46 HB-71(HOCHIKI)
HB-54(HOCHIKI)
IS-24* HD-3(HOCHIKI) SB-46 HB-71(HOCHIKI)
HB-54(HOCHIKI)
Only one detector can be supported in alarm per zone.
If using a mix of System Sensor and other smoke detectors, a maximum of 20 detectors shall be permitted.
Sync Module Compatibility - Panel is compatible with the following synchronization modules:
Amseco #SMD10-3A, Gentex #AVSM, System Sensor #MDL, Wheelock #DSM12/24 *UL and ULC Listed